Repository navigation
Conversation
…negative tests MMS Write: fail closed on invalid single-variable response cardinality
P0 MMS: fail-closed abbreviated DatSet/RptID cross-RCB routing (#707)
…t fallback projection
P8 reporting: reject type-conflicting structured MMS FCD leaves before scalar projection
…continuity evidence
… bounded overflow
…change Remove receive-hot-path registry lock and per-frame Where/ToArray allocation; atomically clear stale session targets on disconnect. Add association reset regressions and repeatable four-RCB BER allocation/throughput telemetry without CI-host-dependent speed gate.
…B delivery at reset Make exact RptID routing single-pass, defer affinity/DatSet scans, preserve fail-closed identity precedence. Add nonblocking producer admission lease so stopped RCBs drain without late delivery; protect volatile stopped state. Add allocation and concurrency regressions.
…d enrichment budget Use read-only round-robin across observed indexed client slots rather than first 64 sorted BRCBs, which monopolized the budget on a few of 35 families on the BCUNR field profile. Never infer DatSet/availability from name. Distinguish completed budget from complete coverage and add synthetic 35x16 regression.
P9: four-RCB initial report registration race + bounded per-RCB delivery
P9: representative live RCB family enrichment within fixed MMS read budget
Preserve P9 source tree; bring in tested checkout workflow pins, published Pages verification and newer test tool versions. Resolve the sole test-project version overlap in favor of main while retaining Xunit global using. This is staging reconciliation only; production promotion requires exact combined CI and P0 control review.
Cross-repo SG7_BCU P9 physical diagnostic — 2026-11-22 (evidence only, NO engine promotion)Owner-supplied ARSAS field diagnostic from app 1.6.46+cd4b261d and pinned engine BRCB_REPLAY_PROVEN logs on A01/B01 use original EntryID and six-byte MMS BinaryTime TimeOfEntry preceding association by at least 2 minutes; BinaryTime has no clock-sync quality byte, so do not equate TimeOfEntry with process-value Consumer ARSAS PR #793 remains DRAFT: adds bounded exact cross-RCB SOE repeat suppression, one operator control audit ledger, distinct clock-domain hover explanation, and literally blank Quality for command (no badge/placeholder). No changes made here to engine protocol code or ARSAS pinned engine source. Preserve independent RCB continuity, no automatic PurgeBuf and no false lossless SOE/clock certification; physical rerun against the patched binary remains a qualification gate. |
CURRENT PROMOTION AUTHORITY — 2026-11-21
Current staging HEAD:
8f7b75f15f06bb04489283ed0088565a2b3cd2b5, a true two-parent merge of P9 engine stagingfb981b1e622ed298ccf26b71f49aaf21bdc897bbwith latest main1b7ec46754a765d6f7e7b8a512761b18505b2b2a. All current main commits are ancestors of this HEAD. The only overlapping changed file was the test project: we retained exact newer main test dependency versions and the existing Xunit global using. We also preserved main checkout-pin workflows and Pages verification without touching P9 runtime code.P9 engine integration: #200 and #203 MERGED TO STAGING. SHA
fb981b1e...had treef1ead6e10cd04249422ac226ae4ecc6dc69cd1d7exactly equal to field-tested experimental engine24077e48.... Staging HEAD after reconciling maintenance has changed only CI/test/Pages paths relative to that source tree. Actual SG7 operator-trial consumer ARSASa3dca3e8...demonstrated 77/77 Report-backed values and 4/4 true RCB InformationReport ingress.This remains a DRAFT / NO PRODUCTION PROMOTION. The combined exact-SHA staging Windows .NET CI #44806482535 has now completed SUCCESS on
8f7b75f15f06bb04489283ed0088565a2b3cd2b5, including build, tests and public-source verification. This is a code-qualification result, not physical control/FAT, consumer installer or mainline production acceptance. Release blockers remain P0 #172 control cleanup/Operate stall risk, reporter ARSAS #769 continuity/reconnect qualification, structured FCD/partial discovery limitations where applicable (#159/#162), consumer integration against latest ARSAS source and physical/FAT signoff. Do not touch ARSAS production lock or public v1.6.42 based solely on successful staging CI.Historical promotion discussion (before current staging P9 integration)
ARIEC61850 promotion gate — staging → main (DRAFT, NOT RELEASE)
Pinned initial staging merge:
b3688be62f255ec5cfd8dfccc2d1d1093c301f62; current staging HEAD:44ac7554f43f2ba06763f3895242cb569b2e6a1c, merged from #190 intostagingwith complete original commit ancestry. Pinned baseline main:3d21238d0b62f24faecd5948a4ee238c82b35966(CI-only #191). Staging is 222 commits ahead and 0 behind at creation; 117 changed files, source changes not yet in main.Staging content
Canonical consolidated sources: #189 (Ed2 prefixed LN/typed DPC), #186 (RCB enrichment negotiated window), #187 (SBOw stage timing), #182 (SCL Ed2.2 identity), #170 (RIO sidecar), #130 (sustained SV analysis), #138 (primary-type semantics), plus historic stacked ancestors #184/#183/#181/#179/#177/#173/#169/#157/#153/#145. Other original PRs were closed as consolidated without direct main merge, with exact source SHA evidence.
CI already proven (staging ingress)
14b19d30466fd296ad1e6d0bddcdd574992bc464synthetic-merge run #39778971482: 1,262/1,262 Windows tests pass, zero compilation warnings/errors, source verify/package/artifacts. The tested target3d21238was byte-identical tostagingbase at that point.b3688be62f255ec5cfd8dfccc2d1d1093c301f62.44ac7554against main3d21238: run #39782663272 — 1,262/1,262 tests, zero build warnings/errors, source/provenance, restore, package, diagnostics artifacts. Checkout verified asrefs/pull/192/mergeat0c142ec. Recheck if either base/head changes.Release / physical field gates (not satisfied by CI)
SG7_BCUSystem/Bkr0XCBR1.PosSBO enhanced versus ARSAS Command Dock initialSG7_BCUMaster/GGIO2.DPCSO01DO normal. Never infer breaker control owner from status alone or GGIO name; require exact ctlModel/type/service evidence, unambiguous equipment association and operator confirmation. No live operate test is authorized here. Preserve existing successful protocol-control implementation.Merge policy: This PR remains DRAFT until those gates are explicitly satisfied; no automatic production release, version bump or ARSAS repin. Avoid creating any more CI-only PRs. All work tracked here and central engineering issue #144.
Verified staging housekeeping — 2026-10-22
Staging updated by commit
44ac7554f43f2ba06763f3895242cb569b2e6a1ccontaining only test dependency upgrades from old #171: coverlet.collector 10.1.0, Microsoft.NET.Test.Sdk 18.11.0, xunit.runner.visualstudio 4.0.1, retaining<Using Include="Xunit" />that the outdated old PR would have dropped. This was not merged intomain. Windows CI onrefs/pull/192/mergepassed 1262/1262 tests with zero compilation warnings/errors (run #39782663272). Main promotion remains blocked by open control/IED interoperability FAT gates and three genuinely divergent source branches.Final source-PR reconciliation (2026-10-22)
725662b004b74c3743943f83f3bcf93b745f7823; currentmainbase remains3d21238d0b62f24faecd5948a4ee238c82b35966. Git compare: staging 227 ahead / 0 behind; 121 changed files. Never reapply legacy PR file snapshots on top of staging.d086ed5b03aeb45c91ad37cefbc8b5b5627a2718. Two source/test blobs exact from old Discovery P7.7: bounded DataSet-first type closure beyond GetNameList limit #155, two additive changes to latest source preserving negotiated-window RCB/control behavior. CI #39787085722: 1,264/1,264 PASS.725662b004b74c3743943f83f3bcf93b745f7823, CI #39788026745: 1,269/1,269 PASS, 0 warnings/errors. All 5 tests added; none of latest engine code overwritten. Old source PR closed as functionally superseded, NOT Git ancestor.725662b004b74c3743943f83f3bcf93b745f7823PASSED: run #39788648767, checkout verifiedrefs/pull/192/mergeat9321410againstmain3d21238; 1,269/1,269 tests PASS, 0 build warnings, 0 build errors. Includes source/provenance, restore, Release build, package and diagnostics. Any staging/main head change requires a fresh run.masarray/arsasproductionmainlock still engine P10.9U: verify standard Pos status with one typed read on truncated NameList #169 (036e2c00...), live FAT trial #679/#680 lock engine P0-C: classify SBOw 400ms safety-observation latency and reject delayed LastApplError before Operate #184 (9c7cb403...), #666 timing trial uses P0 SBO Enhanced: per-invoke TPKT send / confirmed response / decode timing (no safety change) #187 (4ed76ccd...). No automated repin, no silent consumer promotion; need pinned combined ARSAS build+field-qualified control/RCB/SV tests, GE SG7_BCU correctBkr0XCBR1.Poscontrol and vendor parity. Engine issues P0 investigation: consecutive BCUGE Operate stalls and unbounded cancellation cleanup #172/P10.6: complete GE F650 MMS NameList beyond 64-page smart-discovery budget without latency regression #162/P8 C264: schema-verified structured FCD report projection and rejection evidence #159 remain open. Protectmainfrom direct push when admin controls are available.Do not convert this PR out of DRAFT or merge into main solely from green engine unit tests.